A COMMON CUSTOMER COMPLAINT: "My Hot Water Stinks"David J. Hack Water Specialist Missouri Department of Natural Resources Jefferson City, MO Although taste and odor problems can affect both hot and cold water, usually hot water causes more complaints - especially complaints about the rotten egg stench. A number of conditions can contribute to the occurrence of these odors. This article reviews a few of the basics relating to the formation of rotten egg odors, especially those associated with hot water. Sulfates in water will chemically reduce to sulfides
by natural chemical processes; however, a microorganism catalyst is required
for this reaction to take place at a significant rate. Non-pathogenic anaerobic
bacteria, such as Desulfuvibrio desulfuricans, form enzymes as a
metabolic function that have the power to accelerate the sulfate-reduction
reaction by decreasing the activation energies of the reaction. The subsequent
production of hydrogen sulfide gas creates the distinctive rotten egg odor.
Excess electrons
The sulfate-reducing bacteria require an external
source of energy in order to participate as the catalyst in the sulfate-reduction
reaction. This energy source is provided by the excess electrons released
by oxidation of organic matter or corrosion of metals.
Complaints of rotten egg odors are more common
for hot water than cold. The solubility of the hydrogen sulfide decreases
as the temperature increases, causing the gas to be expelled when hot water
is released from the tap. Sulfate-reducing bacteria activities in the groundwater
aquifer, distribution system, or hot water heater tank may all be responsible
for the hydrogen sulfide concentration.
Oxidation
The concentration of hydrogen sulfide in the water
of an aquifer is dependent on the environment in which the bacteria must
work. The energy source for the bacteria in the aquifer is primarily the
oxidation of organic matter. The oxidation of the organics may be slowed
by the lack of essential nutrients for bacterial growth. A low rate of
oxidation of organics would results in a low source of energy to be utilized
by the sulfate-reducing bacteria; this, in turn, would result in a low
concentration of hydrogen sulfide.
Hydrogen sulfide may be effectively oxidized to
sulfur or sulfates by chlorination. The chemical reaction of sulfide oxidation
by chlorination may be represented by two equations:
CI2 + S2 - 2 CI + S (1)
4CI2 + S2 +4H2O
- 8 HCI + SO4-2 (2)
The oxidation to sulfur (Eq 1) is an instantaneous
primary reaction. The secondary reaction of oxidation to sulfate (Eq 2)
may take place simultaneously or proceed at a slower rate, depending on
pH and concentration of reactants. Optimum pH ranges are 6.5 to 8.5, with
the secondary oxidation rate increasing sharply between pH 6.5 and pH 7.3.
Theoretically, 8.5 mg/L of chlorine are required
for each 1 mg/L of hydrogen sulfide to assure complete chemical oxidation.
It may be most economical to reduce the hydrogen sulfide concentration
by aeration prior to chlorination.
Maintain chlorine residuals
It is important to maintain chlorine residuals throughout
the distribution system in order to suppress the growth of sulfate bacteria.
If existing chlorine residuals are exposed to excess bacterial activity
in the distribution system, the results can be a reduction in the residual
levels. Bacterial activity then increases the corrosion rate, which in
turn increases bacterial activity, since excess electrons to be utilized
by the bacteria are provided by the corrosion of the metal. Therefore,
bacterial activity in the system in the absence of adequate chlorine residuals
causes not only odor problems by also certain types of corrosion of distribution
mains.
Chlorine depletion and related problems are made
worse by the stagnant water environment of dead-end lines, where bacteria
can flourish. Looping of distribution lines to eliminate dead ends and
periodic flushing of low-flow lines can reduce the concentration of the
sulfate-reducing bacteria and help to avoid the problems they cause.
Cathodic protection
The method used to provide corrosion protection of
most water heater tanks can produce an environment that is ideal for the
production of hydrogen sulfide gas. Modern water heaters are glass-lined
to prevent corrosion, but assuring 100 percent glass coverage protection
is impossible, especially since cracks or voids in the glass coating may
occur, a long magnesium rod, an "anode," is used to provide cathodic protection.
Because of the relative position of magnesium to steel in the electromotive
series of metals, magnesium will corrode, producing an abundance of electrons
that coat the exposed steel surface. There will be no corrosion of the
exposed steel so long as the magnesium anode remains in the tank and has
not been totally sacrificed to protect the tank wall.
The number of electrons liberated by the sacrifice
of the magnesium anode is far greater than the amount required to protect
the exposed steel of the water heater tank. The excess electrons provide
the external energy source required by the sulfate-reducing bacteria to
participate as the catalyst in the sulfate-reducing reaction.
Ion-exchange water softener
A frequent contributor to the odor problem is the
ion-exchange water softener. The softened water is more corrosive than
the water was before calcium and magnesium ions were exchanged for sodium
ions. Therefore, the use of a softener increases the rate at which the
magnesium anode is sacrificed. This provides more energy to the bacteria,
accelerating the rate of sulfate reduction and increasing the odor complaints.
Remedy for rotten egg odor
Maintaining chlorine residuals.
Maintaining a chlorine residual of 1 mg/L throughout the distribution system
oxidizes any hydrogen sulfide present and inhibits bacterial activity and
corrosion associated with sulfate-reducing bacteria. In a nonchlorinated
system, periodic disinfection and flushing of the water heater tank with
a chlorine bleach solution may be sufficient. If the problem is severe
or persistent, a chlorine feeder system may be required.
Flushing distribution lines.
Flushing of low-flow lines and looping of distribution lines and looping
of distribution lines to eliminate dead ends can reduce the concentration
of the sulfate-reducing bacteria and help to alleviate the problems they
cause.
Killing bacteria with heat.
The thermal death point of sulfate-reducing
bacteria is approximately 1400 F (600 C). Water heaters
are usually factory set at 1400 F +/- 100 F (600
C +/- 60 C), which is the "medium" setting on the temperature
control dial. Increasing the temperature to the "high" setting (1600
F, or 710 C) for several hours and flushing the tank should
kill the sulfate-reducing bacteria and greatly reduce the odor problem
until the population of the bacteria becomes high again.
CAUTION:
The hot water tank must have an operable pressure relief valve; otherwise, this
method of treatment may be dangerous. The temperature setting must be reduced
following treatment to eliminate the risk of persons being scalded from
dangerously hot water and to avoid high energy cost.
Replacing magnesium anode rods.
Zinc has an electrode potential that is much closer to that of the steel
tank than magnesium. If a zinc anode is used instead of magnesium, the
zinc will sacrifice fewer excess electrons to reduce the sulfates. This
remedy will not eliminate problems associated with sulfate-reducing bacteria,
but it can greatly reduce them.
Removing cathodic-protection anode.
Removal of the cathodic-protection anode is not a preferred method, but
it may alleviate the odor problem. The method eliminates all cathodic protection
from the tank, which may shorten tank life, especially where water softeners
are in use.
|